Bryant Breaker Twin
![]() |
![]() BRYANT BR15 20 TWIN POLE 15AMP 20AMP CIRCUIT BREAKER US $29.95
|
![]() BRYANT BRD BD1520 BD15 20 1 pole 15 amp 20 amp TWIN Breaker US $29.50
|
![]() BRYANT tandem TWIN 15 amp BRSN brsn215 breaker NEW US $26.99
|
![]() BRYANT BD15 15 TWIN POLE 15AMP 120 240V CIRCUIT BREAKER US $24.95
|
![]() BRYANT BD20 15 TWIN POLE 15AMP 20AMP CIRCUIT BREAKER US $24.95
|
![]() bryant twin bd bd20 20 bd2020 20 20 amp CIRCUIT BREAKER US $19.99
|
![]() BRYANT 15 AMP TWIN BREAKER BRD BD15 15 US $15.95
|
![]() 2 NEW BD3030 BRYANT 30 30 BREAKER 30A 2 1P DUPLEX TWIN US $14.95
|
![]() Westinghouse Bryant 20A 20 Amp Twin Tandem Circuit Breaker BD2020 US $13.95
|
![]() bryant breaker twin bd bd20 15 bd2015 20 15 amp US $9.99
|
![]() Bryant BD1515 Circuit Breaker Twin 15 Amp 120 240V US $9.99
|
![]() BRYANT BRD BD1515 BD15 15 1 pole 15 amp TWIN Breaker US $6.99
|
![]() Bryant Twin BD20 20 circuit breaker US $9.00
|
![]() Bryant Twin BD15 15 circuit breaker 15A 15A US $9.00
|
![]() Bryant Murray 15 Amp Twin Breaker Type BRD EPD US $5.00
|
Hot to ground 120V,Hot to neutral 60V?
When I use a plug checker it says outlet wired correctly. plug in lamp,no light. I am working with
Wirecon self contained receptacles.At the panel there is a Bryant 15A twin breaker. 2 circuits on the same phase.I get 120V from breaker to neutral and to ground. I move 1 of the circuits to a 1P15A breaker,same problem. Any clues.
There is no legitimate way to get 60 Volts.
The way residential is wired, you can only get 120 Volts, or 240 Volts.
The only way I can imagine is if you have a loose neutral wire, or floating ground wire, but then that could likely affect all circuits.
Check your neutral wires --- that is likely the problem.
Maybe a loose neutral wire somewhere.